| Product | Type | Plates | Max Flow |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | 53x52 | 74.41 GPM |
Note: Unit pictured is representative of standard unit and may not exactly depict p/n B16Hx53x52 as shown on this page.
This is the 53x52-plate B16: SWEP designation B16Hx53x52. The H plate is the obtuse chevron: it gives the most heat transfer per plate and the most pressure drop, so it suits duties where approach temperature matters more than pump head. The B16 plate pack measures 376 x 119 mm (14.8 x 4.69 in) on 320 x 63 mm port centres. Maximum flow for the frame is 16.9 m3/h (74.41 GPM); that is a ceiling for the ports, not a duty point. If the flow on either side would exceed the published ceiling, the answer is a larger frame, not more plates on this one.