| PRODUCT | TYPE | STYLE | MAX FLOW |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | Copper Brazed | 335.50 GPM |
The dual circuit here is a true one - two independent refrigerant paths sharing one plate pack and one water circuit.
Two refrigerant paths, one water circuit. 693 x 243 mm with up to 220 plates - the tall frame of the 200-400 band, with 0.335 dm3 channels.
For a two-compressor chiller that is the difference between staging capacity properly and running one oversized circuit at part load. It also gives redundancy: a failed compressor takes out half the machine rather than all of it, which is worth more over a plant's life than a point of full-load efficiency.
Threaded, solder and flange connections. 316/316L plates with copper brazing and PED, UL and KHK approvals - and at 17.5 kg empty plus 567 grams a plate, a full pack is a two-person lift into the frame.
Reading the part number. A B57 is ordered as a full string - frame, plate type, plate count, pass arrangement, materials and pressure class, for example B57H/D-SC-S. Every field is decodable: the model number guide explains each one, and the string off your nameplate, complete or partial, is enough for us to confirm the build and quote it.
The B57 measures 693 x 243 mm (27.28 x 9.57 in) over the plate pack, with port centres of 600 x 148 mm (23.62 x 5.83 in). Connections on the catalogued builds: Threaded, Solder, Flange.
SWEP publishes the weight as 17.51 kg plus 0.567 kg per plate, so the plate count off the nameplate sets what the mounting has to carry.
The 693 mm height is the retrofit catch - it stands 168 mm taller than the B45/B120T family and their brackets will not carry over.