| PRODUCT | TYPE | STYLE | MAX FLOW |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | Copper Brazed | 123.28 GPM |
FI190 belongs to the newer 60 to 150 kW range built specifically for the low-GWP refrigerants, and works as evaporator or condenser.
Part of the 60 to 150 kW low-GWP range. 524.5 x 202 mm, up to 140 plates and 123.28 GPM, working as evaporator or condenser for R32, R454B and R290 systems.
The design problem it answers is charge. A2L and A3 refrigerants carry charge limits written in kilograms, and every liter of internal volume in the exchanger counts against that limit. Integrated distribution keeps the hold-up volume down, which is what buys headroom under the limit or a larger machine at the same limit.
Integrated distribution, standard connections. Threaded, Victaulic and solder options on 316 plates with copper brazing; PED, UL and KHK approvals; asymmetric 0.149/0.172 dm3 channels.
Reading the part number. A FI190 is ordered as a full string - frame, plate type, plate count, pass arrangement, materials and pressure class, for example FI190H/1P-NSC-H. Every field is decodable: the model number guide explains each one, and the string off your nameplate, complete or partial, is enough for us to confirm the build and quote it.
The FI190 measures 524.50 x 202 mm (20.65 x 7.95 in) over the plate pack, with port centres of 460 x 136 mm (18.11 x 5.35 in). Connections on the catalogued builds: Threaded, Victaulic, Solder.
SWEP publishes the weight as 6.45 kg plus 0.289 kg per plate, so the plate count off the nameplate sets what the mounting has to carry.
On A2L and A3 systems the exchanger's internal volume counts against the charge limit - quote the duty, not just the footprint, when sizing a replacement.
Call and talk it through with an engineer: 1-805-484-2992