| PRODUCT | TYPE | STYLE | MAX FLOW |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | Copper Brazed | 272.98 GPM |
B224 was introduced alongside the B327 for data center cooling and district heating.
Introduced for data centers and district heating. 620 x 202 mm, up to 300 plates and 272.98 GPM, designed alongside the B327 with one stated priority: large ports for high flow at low pressure drop.
The design priority is stated plainly by SWEP: large ports for high flow rates, low pressure drop, high thermal efficiency. In a coolant distribution unit the pressure drop across the exchanger is parasitic load for the life of the facility, so port size is not a packaging detail - it is the operating cost.
O-ring and Victaulic options among the connections. 304 plates with copper brazing, threaded and flange variants catalogued, PED, UL and KHK approvals.
Reading the part number. A B224 is ordered as a full string - frame, plate type, plate count, pass arrangement, materials and pressure class, for example B224M/1P-NC-S. Every field is decodable: the model number guide explains each one, and the string off your nameplate, complete or partial, is enough for us to confirm the build and quote it.
Large ports for coolant distribution and district energy - flow without parasitic head.
Request a Quote
The B224 measures 620 x 202 mm (24.41 x 7.95 in) over the plate pack, with port centres of 530 x 112 mm (20.87 x 4.41 in). Connections on the catalogued builds: Threaded, Victaulic, Flange, O-Ring.
SWEP publishes the weight as 6.84 kg plus 0.322 kg per plate, so the plate count off the nameplate sets what the mounting has to carry.
At 6.84 kg empty plus 322 grams a plate, even a 300-plate build stays around 100 kg - light for its duty class, which the mounting design can use.
Call and talk it through with an engineer: 1-805-484-2992