| PRODUCT | TYPE | STYLE | MAX FLOW |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | Copper Brazed | 192.41 GPM |
D2P means dual circuit over two passes - two refrigerant circuits, each making two passes of the pack.
The dual-over-two-pass member of the 525 x 243 family. Up to 250 plates and 192.41 GPM on the footprint it shares with the B45 and B120T.
It is a configuration that only makes sense at some scale, which is why it appears here and on the B12 rather than on the small frames. For a staged chiller that needs a close approach on both circuits, it is the arrangement to ask about, and it removes a second exchanger and its pipework from the bill of materials.
Compact flange and Victaulic options. 316/316L plates with copper brazing, threaded and solder connections also catalogued; PED, UL and KHK approvals.
Reading the part number. A B200T is ordered as a full string - frame, plate type, plate count, pass arrangement, materials and pressure class, for example B200TH/D2P-SC-S. Every field is decodable: the model number guide explains each one, and the string off your nameplate, complete or partial, is enough for us to confirm the build and quote it.
Dual-over-two-pass on the 525 x 243 mm frame - staged chillers with a close approach.
Request a Quote
The B200T measures 525 x 243 mm (20.67 x 9.57 in) over the plate pack, with port centres of 448.50 x 163.50 mm (17.66 x 6.44 in). Connections on the catalogued builds: Threaded, Victaulic, Solder, Combo.
SWEP publishes the weight as 12.62 kg plus 0.4 kg per plate, so the plate count off the nameplate sets what the mounting has to carry.
A D2P pack is not reversible into a single-circuit duty - confirm the circuit arrangement on the nameplate before quoting a swap.
Call and talk it through with an engineer: 1-805-484-2992