| Product | Type | Plates | Max Flow |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | 100 | 120.64 GPM |
Note: Unit pictured is representative of standard unit and may not exactly depict p/n B120THx100/1P-SC-S 4x2"(54) as shown on this page.
The B120THx100/1P-SC-S 4x2"(54) is a 100-plate build of the SWEP B120T. The H plate is the obtuse chevron: it gives the most heat transfer per plate and the most pressure drop, so it suits duties where approach temperature matters more than pump head. The /1P-SC fields read as single pass, with 316/316L stainless steel plates and a copper braze. The closing S is the pressure class: 31 bar at 155 C. Connections are listed as 4x2"(54), in port order. The B120T plate pack measures 525 x 243 mm (20.67 x 9.57 in) on 456 x 174 mm port centres, and by SWEP's published weight formula a 100-plate unit comes to about 48.7 kg (107.4 lb) dry. Maximum flow for the frame is 27.4 m3/h (120.64 GPM); that is a ceiling for the ports, not a duty point. If the duty has changed since the original equiptment went in, send the flows and both inlet conditions and we will confirm whether this configuration still fits.