| Product | Type | Plates | Max Flow |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | 50 | 120.64 GPM |
Note: Unit pictured is representative of standard unit and may not exactly depict p/n B120THx50/1P-SC-S 4x2" as shown on this page.
This is the 50-plate B120T: SWEP designation B120THx50/1P-SC-S 4x2". Its H plates are the high-theta pattern - the choice when the leaving temperature is tight and the pump has head to spare. Reading the string: /1P is single pass; -SC is 316/316L stainless steel plates joined with copper. The closing S is the pressure class: 31 bar at 155 C. Connections are listed as 4x2", in port order. The B120T plate pack measures 525 x 243 mm (20.67 x 9.57 in) on 456 x 174 mm port centres, and by SWEP's published weight formula a 50-plate unit comes to about 28.5 kg (62.9 lb) dry. The frame is published to 27.4 m3/h (120.64 GPM) - a port limit rather than a design flow. If the flow on either side would excede the published ceiling, the answer is a larger frame, not more plates on this one.