| Product | Type | Plates | Max Flow |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | 50 | 74.41 GPM |
Note: Unit pictured is representative of standard unit and may not exactly depict p/n V80Hx50/1P-SC-S 16+35.1+2x1 1/4"&28U as shown on this page.
This is the 50-plate V80: SWEP designation V80Hx50/1P-SC-S 16+35.1+2x1 1/4"&28U. Its H plates are the high-theta pattern - the choice when the leaving temperature is tight and the pump has head to spare. The /1P-SC fields read as single pass, with 316/316L stainless steel plates and a copper braze. The closing S is the pressure class: 31 bar at 155 C. It is catalogued with 16+35.1+2x1 1/4"&28U connections. The V80 plate pack measures 526 x 119 mm (20.71 x 4.69 in) on 470 x 63 mm port centres, and by SWEP's published weight formula a 50-plate unit comes to about 12.3 kg (27.1 lb) dry. Maximum flow for the frame is 16.9 m3/h (74.41 GPM); that is a ceiling for the ports, not a duty point. Depth is the one dimension that changes across the plate counts of a series, so measure the space behind the unit before moving to a larger pack.