| Product | Type | Plates | Max Flow |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | 100 | 192.41 GPM |
Note: Unit pictured is representative of standard unit and may not exactly depict p/n V200THx100/1P-SC-M 35.1+66.8+2x2" as shown on this page.
This is the 100-plate V200T: SWEP designation V200THx100/1P-SC-M 35.1+66.8+2x2". The H plate is the obtuse chevron: it gives the most heat transfer per plate and the most pressure drop, so it suits duties where approach temperature matters more than pump head. Reading the string: /1P is single pass; -SC is 316/316L stainless steel plates joined with copper. The closing M is the pressure class: up to 45 bar at 135 C, fatigue tested. The connection field reads 35.1+66.8+2x2". The V200T plate pack measures 525 x 243 mm (20.67 x 9.57 in) on 448.5 x 163.5 mm port centres, and by SWEP's published weight formula a 100-plate unit comes to about 54.5 kg (120.0 lb) dry. Maximum flow for the frame is 43.7 m3/h (192.41 GPM); that is a ceiling for the ports, not a duty point. A like-for-like order needs only this string; we recommend adding the fluids and flows where the system has been altered.