| Product | Type | Plates | Max Flow |
|---|---|---|---|
| Heat Exchanger | Brazed Plate | 26 | 39.63 GPM |
Note: Unit pictured is representative of standard unit and may not exactly depict p/n B25THx26/1P-SC-M as shown on this page.
The B25THx26/1P-SC-M is a 26-plate build of the SWEP B25T. The H plate is the obtuse chevron: it gives the most heat transfer per plate and the most pressure drop, so it suits duties where approach temperature matters more than pump head. Reading the string: /1P is single pass; -SC is 316/316L stainless steel plates joined with copper. The closing M is the pressure class: up to 45 bar at 135 C, fatigue tested. The B25T plate pack measures 526 x 119 mm (20.71 x 4.69 in) on 479 x 72 mm port centres, and by SWEP's published weight formula a 26-plate unit comes to about 6.7 kg (14.9 lb) dry. Maximum flow for the frame is 9 m3/h (39.63 GPM); that is a ceiling for the ports, not a duty point. If the flow on either side would exceed the published ceiling, the answer is a larger frame, not more plates on this one.